Ados

FlexADOS 914 MED

Multi-channel gas sensor system
FlexADOS 914 MED

Suitability

The multi-channel gas detector system FlexADOS914 MED continuously monitors the ambient air and provides an early warning of harmful, explosive and non-flammable gases and vapours. The evaluation unit has been equipped with a robust cabinet to resist increased mechanical strains as they may occur in the maritime sector. Moreover, the evaluation unit disposes of the class certificate DNV-GL and fulfills the requirements of the Marine Equipment Directive 2014/90/EU (marking: MED wheel mark). Together with the GTR 210 gas transmitter family, FlexADOS 914 MED achieves safety integrity level SIL1 and can be used for primary explosion protection.

Areas of application

  • Explosion protection on ships with LNG drives, LPG drives and LFL drives
  • Explosion protection and interting on LNG, CNG, oil and chemical tankers, 
  • Explosion protection in LNG terminals
  • Liquid gas storage facilities
  • Leakage monitoring of refrigerating units
  • Laboratories
  • Refineries
  • Detection of oxygen deficiency and excess oxygen
  • Gas powered boiler systems
  • Wastewater treatment plants
  • Inertisation.
  • and much more

Features

  • Up to 12 analogue 4...20mA sensors are evaluated (GTR 210 MED)
  • Graphic LCD display to show content values, mean values and faults in plain text
  • Indicator for operation, malfunction, maintenance, power failure
  • Simple menu-guided setting of the device parameters using 6-part keyboard
  • Three alarm thresholds per sensor, independently adjustable from 10 to 90% of the measuring range
  • Averaging from 1 to 60 minutes possible
  • Maximum of 14 potential-free changeover contacts to control further warning and control facilities
  • Potential-free changeover contact for malfunction,maintenance and power failure
  • Optional: Connection to building management systems for transmission of measured values and status

  • Aluminium wall housing (IP 54)
  • High operating reliability
  • Low power consumption
  • Simple assembly
  • Uninterrupted electricity supply possible

Measuring ranges

Gas types can be
adjusted as desired,
Examples:

CH4 methane / LNG
H2 hydrogen
O2 oxygen
CO2 carbon dioxide
H2S hydrogen sulphide
R134a tetrafluoroethane

Physical grouping 

freely adjustable,

Examples:

%LEL
ppm
VOL%

Technical data

Sensors analogue 4...20mA

12 sensors in a

 2- or 3-wire system

Power supply 100-240V 50/60Hz
max. power consumption 60VA
Operating conditions -25°C...+45°C
80kPa...120kPa
0%...95% rel. humidity
non-condensing
Protection class due to housing
(DIN EN 60529)

IP 54

 

Dimensions (WxHxD)

400 x 300 x 130 mm

Displays Graphic LCD display
128 x 64 px
Background red/green/yellow
LED power, malfunction,
power failure, maintenance digital inputs
digital inputs 3
digital outputs 17 relays
per 1 relay
Malfunction, power failure,
maintenance
14 alarm relays
Potential-free change-over
contacts
Max. switching capacity 250V/8A
other interfaces USB
Fieldbus expansion module
(optional)
Weight 7 kg
Service life
Buffer battery clock
Service life parameter memory

> 10 years

> 20 years

 

Storage conditions

max. 1 year

-25°C...+45°C

80kPa...120kPa

0%...95% rel. humidity

non-condensing

Safety level

SIL 1

MED approval:


Certificate number

Use

MED Item 3.54 / SOLAS 74 u.a:

IEC60092-504

IEC60533
MEDB00006DG
under deck

Classification certificate

Certificate number
Classification:
Temperature, 
Humidity,
Vibration,
EMC, 
Enclosure

DNVGL-CG-0339

TAA00002JH
Class
C
B
A
B
B
Labelling EN60079-29-1, EN50104 

Accessories

Horn, warning light, blinker lamp, recorder, emergency power unit UPS 2000-24V, gas cooler, gas inlet, and much more. Additional accessories are offered on request depending on the measuring task.

Universal FieldBus

Optional data interface:

  • LONWorks
  • Modbus RTU
  • Profibus
  • ModBus TCP