FlexADOS 914 MED
Multi-channel gas sensor system
Suitability
The multi-channel gas detector system FlexADOS914 MED continuously monitors the ambient air and provides an early warning of harmful, explosive and non-flammable gases and vapours. The evaluation unit has been equipped with a robust cabinet to resist increased mechanical strains as they may occur in the maritime sector. Moreover, the evaluation unit disposes of the class certificate DNV-GL and fulfills the requirements of the Marine Equipment Directive 2014/90/EU (marking: MED wheel mark). Together with the GTR 210 gas transmitter family, FlexADOS 914 MED achieves safety integrity level SIL1 and can be used for primary explosion protection.
Areas of application
- Explosion protection on ships with LNG drives, LPG drives and LFL drives
- Explosion protection and interting on LNG, CNG, oil and chemical tankers,
- Explosion protection in LNG terminals
- Liquid gas storage facilities
- Leakage monitoring of refrigerating units
- Laboratories
- Refineries
- Detection of oxygen deficiency and excess oxygen
- Gas powered boiler systems
- Wastewater treatment plants
- Inertisation.
- and much more
Measuring ranges
Gas types can be
adjusted as desired,
Examples: |
CH4 methane / LNG
H2 hydrogen
O2 oxygen
CO2 carbon dioxide
H2S hydrogen sulphide
R134a tetrafluoroethane
|
Physical grouping
freely adjustable,
Examples:
|
%LEL
ppm
VOL% |
Technical data
Sensors analogue 4...20mA
|
12 sensors in a
2- or 3-wire system
|
Power supply |
100-240V 50/60Hz |
max. power consumption |
60VA |
Operating conditions |
-25°C...+45°C
80kPa...120kPa
0%...95% rel. humidity
non-condensing |
Protection class due to housing
(DIN EN 60529) |
IP 54
|
Dimensions (WxHxD) |
400 x 300 x 130 mm
|
Displays |
Graphic LCD display
128 x 64 px
Background red/green/yellow
LED power, malfunction,
power failure, maintenance digital inputs |
digital inputs |
3 |
digital outputs |
17 relays
per 1 relay
Malfunction, power failure,
maintenance
14 alarm relays
Potential-free change-over
contacts
Max. switching capacity 250V/8A |
other interfaces |
USB
Fieldbus expansion module
(optional) |
Weight |
7 kg |
Service life
Buffer battery clock
Service life parameter memory |
> 10 years
> 20 years |
Storage conditions
|
max. 1 year
-25°C...+45°C
80kPa...120kPa
0%...95% rel. humidity
non-condensing
|
Safety level
|
SIL 1
|
MED approval:
Certificate number
Use |
MED Item 3.54 / SOLAS 74 u.a:
IEC60092-504,
IEC60533
MEDB00006DG
under deck
|
Classification certificate
Certificate number
Classification:
Temperature,
Humidity,
Vibration,
EMC,
Enclosure |
DNVGL-CG-0339
TAA00002JH
Class
C
B
A
B
B |
Labelling |
EN60079-29-1, EN50104 |
Accessories
Horn, warning light, blinker lamp, recorder, emergency power unit UPS 2000-24V, gas cooler, gas inlet, and much more. Additional accessories are offered on request depending on the measuring task.
Universal FieldBus
Optional data interface:
- LONWorks
- Modbus RTU
- Profibus
- ModBus TCP
- TCP/IP (Webserver)