FlexADOS 914
Multi-channel gas sensor system
Suitability
The multi-channel gas detector system FlexADOS 914 continuously monitors the ambient air and provides an early warning of harmful, explosive and non-flammable gases and vapours. Together with the GTR 210 gas transmitter family, FlexADOS 914 fulfils EN 50271:2011, achieves safety integrity level SIL1 and can be used for primary explosion protection.
Areas of application
- Explosion protection chemicals industry
- Paint and varnish manufacturing
- Liquid gas storage facilities
- Laboratories
- Refrigerated warehouses (ammonia monitoring)
- Refineries
- Measurement of oxygen concentration
- Gas-powered boilers
- Wastewater treatment plants
- and much more
Features
- Up to 12 analogue 4...20mA sensors are evaluated (GTR 210, LCTR 903, TOX 592)
- Graphic LCD display to show actual values, mean values and faults in plain text
- Indicator for operation, malfunction, maintenance, power failure
- Simple menu-guided setting of the device parameters using 6-part keyboard
- Three alarm thresholds per sensor, independently adjustable from 10 to 90% of the measuring range
- Averaging from 1 to 60 minutes possible
- Maximum of 14 potential-free changeover contacts to control further warning and control facilities
- Potential-free changeover contact for malfunction, maintenance and power failure
- As an option: Building control system connection for data transfer (measuring value and state)
- Plastic wall housing (IP 54)
- High operating reliability
- Low power consumption
- Simple assembly
- Uninterrupted electricity supply possible
Measuring ranges
Gas types can be
adjusted as desired,
Examples: |
CH4 methane
H2 hydrogen
H2S hydrogen sulphide
CO2 carbon dioxide |
physical unit
adjustable as desired,
Examples: |
%LEL
ppm
VOL% |
Technical data
Sensors analogue 4...20mA |
12 sensors
in a 2- or 3-wire system |
Power supply |
115 V / 60 Hz
230 V / 50 Hz (optional)
24 V / DC (optional) |
max. power consumption |
60VA |
Operating conditions |
-13°F ...+113°F
80kPa...120kPa
0%...95% rel. humidity
non-condensing |
Protection class due to housing (DIN EN 60529) |
IP 54 |
Dimensions (WxHxD) |
11,8 x 9,06 x 4,73 inch |
Displays |
Graphic LCD display 128x64 px
Background red/green/yellow
LED power, malfunction,
power failure, maintenance |
digital inputs |
3 |
analogue outputs |
2 x power output 4...20mA
max. burden 400 ohm |
digital outputs |
17 relays
per 1 relay
Malfunction, power failure,
maintenance
14 alarm relays
Potential-free change-over
contacts
Switching capacity max 250V / 8A |
other interfaces |
USB
Universal FieldBus (option) |
Weight |
approx. 3 lbs |
Service life
Buffer battery clock
Service life
Parameter memory |
> 10 years
> 20 years |
Storage conditions |
max. 1 year
-13°F ...+113°F
80kPa...120kPa
0%...95% rel. humidity
non-condensing |
Conformity
EC type-examination according to |
EN60079-29-1
EN50104
EN45544-1
EN50271
EN50270 |
EX marking |
Ex II (2) G |
Accessories
Horn, warning light, blinker lamp, recorder, emergency power unit UPS 2000-24V, gas cooler, gas inlet, and much more. Additional accessories are offered on request depending on the measuring task.
Universal FieldBus
Optional data interfaces for building management systems (BMS)
• LONWorks
• Modbus RTU
• Profibus
• ModBus TCP
• TCP/IP (Webserver)